Air Balancing for Commercial HVAC Systems
Hot offices next to cold meeting rooms, whistling diffusers, doors that slam because of pressure: most of these are airflow problems, not equipment problems. We measure the air at every outlet and set the system to its design.
What is air balancing?
Air balancing is the process of measuring the air flow at every fan, duct branch, diffuser and grille in an HVAC system and adjusting dampers and fan speeds until each one delivers its design flow. It covers supply, return, fresh and exhaust air, and finishes with a report of design against measured values. It is done at handover and whenever a system underperforms.
Reviewed by the MSTECK engineering team · Updated
At a Glance
- Systems
- AHUs, FAHUs, FCUs, ducted units, extract and fresh air fans
- Measured
- Airflow at every terminal, duct traverses, fan pressures and speeds
- Adjusted
- Volume control dampers, fan speeds, pulleys or VSD settings, VAV boxes
- Standards
- ASHRAE 111, NEBB procedures, CIBSE Code A, or your specification
- Tolerance
- As specified, typically within 10% of design at each terminal
- Output
- Balancing report with design and measured values for every outlet
What Air Balancing Covers
A system can have the right equipment and still perform badly when the air goes to the wrong places. Balancing finds where the air is going and puts it where it should be.
- Supply air: every diffuser, grille and slot on each AHU and FCU.
- Fresh air: FAHU and fresh air quantities against the design ventilation rates.
- Return and exhaust: toilet, kitchen and car park extract, and return air paths.
- Room pressure: pressure relationships between spaces, such as kitchens and corridors.
- Fans: duty, static pressure and speed against the design point.
- VAV systems: box minimum and maximum flows checked and set.
Why Choose MSTECK for Balancing
- Engineer-led, with instruments in calibration
- Faults reported clearly: dampers, ducts, fans or controls
- We can fix what the balancing finds, not just report it
- Night and weekend work in occupied buildings
When a Building Needs Air Balancing
Hot and Cold Spots
Rooms on the same system that never reach set point while others are too cold.
Noise and Draughts
Whistling diffusers, high velocity at outlets and draughts at desks.
Doors and Odours
Doors that slam or will not close, and smells moving between spaces.
After a Fit-Out
New partitions or a new layout on a system balanced for the old one.
At Handover
New installations that need a balancing report for the consultant.
High Running Costs
Fans running faster than needed to push air past an unbalanced system.
How an Air Balancing Job Runs
- Review the design. We collect drawings, design airflows and fan data.
- Inspect. Dampers, filters, ducts and fans are checked so the system is ready to balance.
- Measure. Airflow at each terminal and branch, fan pressures and speeds are recorded.
- Adjust. Dampers and fan speeds are set, working from the index run outward.
- Verify. Every outlet is re-measured to confirm it is within tolerance.
- Report. You get the balancing report with readings, settings and any faults found.
What You Receive
- Air balancing report: design and measured flow per outlet
- Final damper positions and fan settings
- Instrument list with calibration certificates
- A list of faults found and what fixing them involves
How We Measure
- Capture hood (flow hood) for supply and extract air at diffusers and grilles
- Digital micromanometer with pitot tube for duct traverses and fan pressures
- Thermal and vane anemometers for face velocities at coils, louvres and openings
- Balancing valve manometer for flow through commissioning valves and PICVs
- Ultrasonic clamp-on flow meter for chilled water flow where no valve can be read
- Thermometers, hygrometer and tachometer for temperatures, humidity and fan or motor speed
Standards We Work To
- ASHRAE Standard 111 for measurement, testing, adjusting and balancing
- NEBB procedural standards for TAB
- CIBSE Commissioning Codes A (air) and W (water) where specified
- Or the consultant's specification and tolerances, where these differ
Every instrument is in calibration, and the certificates go in the report.
What Goes in Your Balancing Report
- Design and measured flow for every terminal, coil and valve, with the percentage of design
- Final settings of dampers, balancing valves, PICVs and fan or pump speeds
- Fan and pump data duty, pressure, speed and motor current against design
- Instrument list with serial numbers and calibration dates
- Issues found such as blocked strainers, missing valves or undersized ducts, with recommendations
Frequently Asked Questions
Why are some rooms colder than others?
Usually because the air is not reaching each room in the right amount. Balancing corrects this, often without replacing any equipment.
Which standard do you balance to?
ASHRAE Standard 111 and NEBB procedures, or CIBSE Commissioning Code A, or the consultant's specification where it sets its own tolerances.
What tolerance do you balance to?
The one in your specification. Without one, we aim for each terminal within 10% of its design flow.
What instruments do you use?
A capture hood, digital micromanometer with pitot tube, thermal and vane anemometers, and a tachometer, all in calibration.
Can you balance while the building is occupied?
Yes. Most of the work is measuring at outlets, which we can do during quiet hours, nights or weekends.
What if the system cannot reach its design flow?
We report why, such as a fan that is too small, a closed fire damper or an undersized duct, and what it would take to fix it.
Do you need the design drawings?
They help. Without them, we can work from the equipment data and a survey of the outlets.
Do you also balance chilled water?
Yes. Air and chilled water balancing are often done together, because a coil needs both its air and its water right.
Which areas do you cover?
Projects across the UAE, including Dubai, Sharjah, Ajman and Abu Dhabi, run from our office in Al Qusais Industrial Area 5, Dubai.
Related Services